TECNAIR R Series in-row air conditioner
Precision air conditioners installed between server racks, from 11.4 to 37.3 kW, as close as possible to the heat produced.
Prices and lead times on quotation. Give the quantity and the context of the installation.
Request a quoteDocumentation
Description
The R Series sits in the rack row, between hot and cold aisles: it draws warm air from the rear and blows cold air from the front, as close as possible to the servers. Front and rear access for maintenance, hydraulic, refrigerant and electrical connections from above or below.
- Survey3 controller: colour display, operating history, USB export, Modbus RTU and IP, BACnet as an option
- SMART COOL refrigerant circuit management, electronic expansion valves
- SMART NET local network between units, up to 60 % energy savings compared with redundant back-up
| Characteristic | Value |
|---|---|
| Models | HRA 121–361 · HRU 20–40 |
| Cooling capacity, direct expansion (kW) | 11,4 – 36,6 |
| Cooling capacity, chilled water (kW) | 24,5 – 37,3 |
| Airflow (m³/h) | 3 200 – 9 000 |
| Sound pressure level (dB(A)) | 51 – 62 |
| Width (mm) | 300 – 600 |
| Depth (mm) | 1 200 – 1 220 |
| Height (mm) | 1 970 – 2 000 |
| Overall weight (kg) | 145 – 235 |
| Controller | Survey3 |
Manufacturer data, given for information only.